Lovato ADXT0554 is an advanced 554 A three-phase soft starter for 380–690 V AC asynchronous motors, featuring a 110–120 V AC or 220–240 V AC auxiliary supply, built-in bypass and in-line or inside-delta connection for standard and heavy-duty applications.
£8,407.16
The Lovato ADXT0554 is an advanced three-phase soft starter designed for controlled starting and stopping of large asynchronous motors in standard and heavy-duty industrial applications. As part of the Lovato ADXT soft starter series, it combines three-phase motor control, integrated protection and flexible starting and stopping functions to help reduce starting current and mechanical stress on motors and driven equipment.
The ADXT0554 features a built-in bypass that reduces power losses and heat generation once the motor reaches normal operating speed. It supports both conventional in-line and inside-delta motor connections and provides constant-current, current-ramp, voltage-ramp and adaptive-control starting modes, giving engineers flexibility when commissioning demanding motor-driven machinery.
With a rated starter current of 554 A and a three-phase 380–690 V AC operational voltage, the ADXT0554 is engineered for high-power industrial motors. It supports motors up to 315 kW at 400 V in an in-line configuration and up to 450 kW at 400 V with an inside-delta connection, while its auxiliary supply accepts 110–120 V AC or 220–240 V AC.
Soft starters progressively control the electrical power supplied to an AC motor during acceleration, helping limit starting current and reduce the mechanical shock associated with direct-on-line starting. For large industrial motors, this can help reduce stress on electrical supplies and mechanical components such as couplings, belts, gearboxes, bearings and driven machinery.
The Lovato ADXT0554 provides three-phase control and multiple starting and stopping algorithms for demanding applications. Once acceleration is complete, the built-in bypass carries the running current efficiently, while support for in-line and inside-delta connections gives system designers considerable flexibility when engineering high-power motor-control installations.
Tick the specs you need, then view products that match.
| Motor Protection | Yes | |
|---|---|---|
| Voltage | 400 V, 480 V, 600 V, 690 V | |
| Phase | Three Phase | |
| Coil / Supply Voltage | 110–240 V AC | |
| Current | 554 A | |
| HS Code | 85044090 | |
| Manufacturer | Lovato Electric | |
| Series | ADXT Soft Starters | |
| Model | ADXT0554 | |
| Product type | Advanced three-phase soft starter | |
| Motor type | Asynchronous three-phase | |
| Rated starter current | 554 A | |
| Rated operational voltage | 380–690 V AC | |
| Auxiliary supply voltage | 110–120 V AC / 220–240 V AC | |
| Rated frequency | 50 / 60 Hz | |
| Number of controlled phases | 3 | |
| Built-in bypass | Yes | |
| Rated motor power, in-line at 400 V | 315 kW | |
| Rated motor power, in-line at 500 V | 400 kW | |
| Rated motor power, in-line at 690 V | 560 kW | |
| Rated motor power, inside delta at 400 V | 450 kW | |
| Rated motor power, inside delta at 500 V | 600 kW | |
| Rated motor power, inside delta at 690 V | 800 kW | |
| Rated insulation voltage | 690 V AC | |
| Rated impulse withstand voltage | 6 kV | |
| Starting modes | Constant current, current ramp, voltage ramp, adaptive control | |
| Stopping modes | Voltage ramp, adaptive control, free-wheel stop, DC braking, soft stop with braking contactor | |
| Programming interface | Graphic LCD display | |
| Cooling system | Forced cooling | |
| Protection rating | IP00 | |
| Operating temperature | -10 to +60 °C, with derating above 40 °C | |
| Storage temperature | -25 to +60 °C | |
| Maximum altitude without derating | 1000 m | |
| Relative humidity | 5–95% | |
| Pollution degree | 3 | |
| Internal bypass contact life | 100,000 operations | |
| Standards | EN 60947-4-2, UL 60947-4-2, CSA C22.2 No. 60947-4-2 |
The ADXT0554 provides controlled starting and stopping of large three-phase asynchronous motors in standard and heavy-duty industrial applications, helping reduce starting current and mechanical stress on motors and driven equipment.
The Lovato ADXT0554 has a rated starter current of 554 A and operates with three-phase motor supplies from 380–690 V AC.
With an in-line connection, the ADXT0554 is rated for motors up to 315 kW at 400 V, 400 kW at 500 V and 560 kW at 690 V. With an inside-delta connection, the corresponding ratings are 450 kW, 600 kW and 800 kW.
Yes. The ADXT0554 incorporates a built-in bypass that reduces power losses and heat generation once the motor has completed its starting sequence.
The ADXT0554 accepts an auxiliary supply of 110–120 V AC or 220–240 V AC, providing flexibility for integration into industrial motor-control systems.
Lovato ADXT soft starters provide industrial engineers, machine builders and panel manufacturers with advanced three-phase motor starting, flexible control and efficient bypass operation for high-power standard and heavy-duty motor applications.