ABB OVR T2 3N 80-275s P TS QS is a pluggable 3+1 Type 2 surge protective device for 230/400 V AC TN-S and TT systems, with Safety Reserve technology, 30 kA nominal discharge current, 80 kA maximum discharge current, 275 V AC maximum continuous operating voltage and remote status signalling.
£595.47
The ABB OVR T2 3N 80-275s P TS QS, order code 2CTB815708R0800, is a high-capacity Type 2 surge protective device (SPD) designed for three-phase plus neutral 230/400 V AC TN-S and TT electrical systems. It is suitable for installation at the origin of an installation, in intermediate distribution boards and close to terminal equipment, providing protection against transient overvoltages generated by indirect lightning strikes and electrical switching events.
The OVR T2 3N 80-275s P TS QS uses a 3+1 protection configuration with four protected lines and a maximum continuous operating voltage Uc of 275 V AC. It provides a nominal discharge current In of 30 kA and a maximum discharge current Imax of 80 kA using the 8/20 µs waveform, together with an impulse-current capability Iimp of 6.25 kA using the 10/350 µs waveform.
ABB's patented Safety Reserve system provides additional protection availability and supports planned preventive maintenance, while integrated QuickSafe technology provides dependable thermal disconnection. Pluggable phase and neutral cartridges, end-of-life indication and TS remote signalling make this SPD particularly well suited to demanding commercial and industrial installations where straightforward servicing and remote condition monitoring are required.
Type 2 SPDs are designed to discharge surge currents generated by indirect lightning strikes and switching operations before damaging transient voltages reach connected equipment. With a 30 kA nominal discharge current, 80 kA maximum discharge current and coordinated 3+1 topology, the ABB OVR T2 3N 80-275s P TS QS provides robust surge protection for demanding three-phase plus neutral TN-S and TT installations.
ABB's patented Safety Reserve system provides an additional protection stage so the SPD is not completely disconnected from the network when the primary protection element reaches end of life. This helps maintain basic protection until maintenance can be performed. Combined with individually replaceable cartridges, end-of-life indication and TS auxiliary contacts, the design supports efficient preventive maintenance and remote SPD condition monitoring.
Tick the specs you need, then view products that match.
| Impulse Current Iimp (kA) | 6.25 kA | |
|---|---|---|
| Series | OVR T2 QuickSafe | |
| ABB order code | 2CTB815708R0800 | |
| EAN / GTIN | 3660308525444 | |
| Product group | Surge Protection Devices | |
| Product type | Type 2 surge protective device | |
| SPD classification | Type 2 / Class II | |
| Standards | IEC 61643-11 / EN 61643-11 | |
| Low-voltage distribution systems | TN-S / TT | |
| Configuration | 3+1 | |
| Number of poles | 4 | |
| Number of protected lines | 4 | |
| Nominal system voltage | 230 / 400 V AC | |
| Maximum continuous operating voltage Uc | 275 V AC | |
| Current type / frequency | AC, 47–63 Hz | |
| Impulse current Iimp (10/350 µs) | 6.25 kA | |
| Nominal discharge current In (8/20 µs) | 30 kA | |
| Maximum discharge current Imax (8/20 µs) | 80 kA | |
| Total current | 80 kA | |
| Voltage protection level Up, L-PE | 1.5 kV | |
| Voltage protection level Up, L-N | 1.4 kV | |
| Voltage protection level Up, N-PE | 1.4 kV | |
| Short-circuit withstand capability Isccr | 100 kA | |
| Follow-current interrupting capability | 0.1 kA N-PE | |
| Ground residual current | <10 µA | |
| TOV withstand, L-N / N-PE | 337 / 1200 V | |
| Maximum backup circuit breaker | 125 A, B or C curve | |
| Maximum backup fuse | 160 A gG/gL | |
| Integrated thermal disconnector | Yes | |
| QuickSafe technology | Yes | |
| Safety Reserve | Yes | |
| Preventive maintenance function | Yes | |
| End-of-life indicator | Yes | |
| Remote signalling | Yes | |
| Normally open auxiliary contacts | 1 | |
| Normally closed auxiliary contacts | 1 | |
| Minimum auxiliary contact load | 12 V DC / 10 mA | |
| Maximum auxiliary contact load | 250 V AC / 1 A | |
| Solid conductor connection | 2.5–35 mm² | |
| Stranded conductor connection | 2.5–25 mm² | |
| Wire stripping length | 12.5 mm | |
| Construction | Pluggable | |
| Phase replacement cartridge | OVR T2 80-275s C QS | |
| Phase replacement cartridge order code | 2CTB815708R2600 | |
| Neutral replacement cartridge | OVR T2 N 80-275s C QS | |
| Neutral replacement cartridge order code | 2CTB815708R2800 | |
| Degree of protection | IP20 | |
| Flammability rating | UL 94 V-0 | |
| Operating temperature | -40 to +80 °C | |
| Maximum operating altitude | 2000 m | |
| Response time | <25 ns | |
| Mounting type | 35 mm DIN rail | |
| Module width | 4 modules | |
| Dimensions (H × W × D) | 95 × 71.2 × 69.4 mm | |
| Dimensions with TS auxiliary contact (H × W × D) | 95.8 × 71.2 × 76.7 mm | |
| Weight | approx. 0.60 kg |
It is a Type 2 surge protective device designed for three-phase plus neutral 230/400 V AC TN-S and TT systems, protecting electrical installations and connected equipment against transient overvoltages caused by indirect lightning effects and electrical switching events.
The device has a nominal discharge current In of 30 kA and a maximum discharge current Imax of 80 kA using the 8/20 µs waveform, together with a 6.25 kA impulse-current capability using the 10/350 µs waveform.
The “s” identifies ABB's Safety Reserve version. The Safety Reserve system provides an additional protection stage that maintains basic surge protection when the primary protection element reaches end of life, allowing maintenance to be planned while the installation retains a level of protection.
The TS version includes remote signalling through one normally open and one normally closed auxiliary contact, allowing SPD condition information to be integrated with suitable monitoring, alarm or building-management systems.
Yes. The device uses pluggable cartridges. The phase replacement cartridge is the ABB OVR T2 80-275s C QS, order code 2CTB815708R2600, while the neutral replacement cartridge is the ABB OVR T2 N 80-275s C QS, order code 2CTB815708R2800.
ABB OVR Type 2 surge protective devices combine high surge-current capability, QuickSafe technology and pluggable construction, with the OVR T2 3N 80-275s P TS QS delivering Safety Reserve preventive maintenance, 80 kA maximum discharge capability and remote status signalling for demanding three-phase plus neutral TN-S and TT electrical installations.
● Service Agreements
Credit Accounts
Our service agreements are built to support long term procurement relationships. By working closely with engineering teams and procurement departments, we help streamline purchasing processes while ensuring consistent access to critical components and sourcing support when it matters most.








● frequently asked questions

At Led Controls Ltd we help engineers source the right automation and control gear with confidence. below are quick answers to what we are asked most often.
We supply all leading manfacturers in our industry. we offer next day delivery on most poplour products.
Your content goes here. Edit or remove this text inline or in the module Content settings. You can also style every aspect of this content in the module Design settings and even apply custom CSS to this text in the module Advanced settings.
Your content goes here. Edit or remove this text inline or in the module Content settings. You can also style every aspect of this content in the module Design settings and even apply custom CSS to this text in the module Advanced settings.
Your content goes here. Edit or remove this text inline or in the module Content settings. You can also style every aspect of this content in the module Design settings and even apply custom CSS to this text in the module Advanced settings.
Your content goes here. Edit or remove this text inline or in the module Content settings. You can also style every aspect of this content in the module Design settings and even apply custom CSS to this text in the module Advanced settings.
● latest blog
LED Controls is a specialist distributor of factory automation and industrial controls, supplying OEMs, machine builders, panel builders and end users throughout the UK and worldwide. As a trusted UK distributor for many of the world’s leading automation manufacturers, we provide industrial control products, technical expertise and bespoke automation solutions backed by outstanding customer service.
2025 has been a big year for LED Controls, and our blog has expanded accordingly. We've covered a wide range of topics across industrial control and factory automation this year. From core technology explainers and new product releases to panel building best practice...