Why Choose the Finder 56.34.9.024.0000 Miniature Power Relay?
The Finder 56.34.9.024.0000 is a robust 12 A miniature industrial power relay designed for reliable electrical switching in industrial automation, machinery control and electrical distribution equipment. Part of the established Finder 56 Series, this general-purpose electromechanical relay features a 24 V DC operating coil and four changeover contacts (4 CO / 4PDT), enabling four independent electrical circuits to be controlled from a single relay.
With a 12 A rated contact current, 250 V AC rated contact voltage and silver nickel (AgNi) contacts, the Finder 56.34.9.024.0000 provides versatile switching performance for appropriately rated industrial loads. Its 490 Ω nominal coil resistance, approximately 49 mA coil current and 1.2 W DC coil consumption make it suitable for integration into compatible 24 V DC control systems.
Designed for convenient installation and maintenance, this four-pole plug-in power relay features a lockable test button and mechanical status indicator. It can be installed using appropriately selected Finder 96 Series relay sockets, including suitable DIN rail mounting arrangements. Its combination of high-current contacts, multiple switching poles and replaceable construction makes it a practical choice for OEM equipment, industrial control panels and electrical maintenance applications.
Key Advantages
- Four changeover contacts (4PDT) enable simultaneous switching of four independent circuits.
- 12 A rated contact current supports a wide range of compatible industrial loads.
- 24 V DC operating coil integrates with common low-voltage industrial control supplies.
- Silver nickel (AgNi) contacts provide established general-purpose switching performance.
- 250 V AC rated contact voltage supports industrial electrical applications.
- 400 V AC maximum switching voltage under specified operating conditions.
- Lockable test button assists commissioning and controlled maintenance procedures.
- Mechanical indicator provides visible confirmation of the relay's mechanical state.
- Plug-in design allows straightforward replacement without soldering.
- Finder 96 Series socket compatibility supports flexible panel installation.
- 5 kV coil-to-contact impulse withstand rating provides electrical insulation between control and switched circuits.
- −40 to +70 °C operating temperature range supports demanding industrial environments.
Key Features
- Finder 56 Series miniature industrial power relay.
- 56.34 four-pole relay configuration.
- 24 V DC nominal coil voltage.
- 4 CO / 4PDT / 4 Form C contact arrangement.
- 12 A rated contact current.
- 250 V AC rated contact voltage.
- 400 V AC maximum switching voltage.
- Silver nickel (AgNi) contact material.
- 490 Ω nominal coil resistance.
- 49 mA nominal coil current.
- Approximately 1.2 W nominal DC coil power.
- 19.2 V DC specified must-operate voltage.
- 4.8 V DC specified must-release voltage.
- 11 ms typical operate time.
- 11 ms typical release time.
- Lockable test button and mechanical indicator.
- Plug-in quick-connect terminals, approximately 4.8 mm wide.
- Finder 96 Series socket compatibility.
- RT I environmental protection category.
- Monostable, non-latching electromechanical operation.
Technical note: The 12 A contact rating applies to appropriately specified switching conditions. The maximum voltage rating and resistive-load switching capacity must not be interpreted as permission to switch every load type at those limits. Motors, contactors, solenoids, LED drivers and other inductive or high-inrush loads require separate assessment against Finder's load-specific ratings.
Four-Pole Power Switching for Industrial Automation
The Finder 56.34.9.024.0000 uses a 24 V DC electromagnetic coil to control four independent changeover contact sets. Each contact provides a common terminal, a normally closed connection and a normally open connection. When the coil is energised, all four contact sets transfer to their operated positions. Removing the coil supply returns the contacts to their normal positions, providing conventional monostable relay operation.
This four-pole changeover arrangement is particularly useful in industrial control systems where a single command must operate multiple functions. For example, separate contacts can be assigned to auxiliary switching, equipment status indication, control interlocking and other suitably rated circuits. The four contacts provide electrical switching flexibility, although they are mechanically linked and must not be treated as independently controlled relays.
The AgNi contact material offers established performance for general-purpose electrical switching. Its cadmium-free composition supports modern industrial equipment design. When selecting the relay for applications involving significant starting currents, repetitive switching or inductive loads, designers should verify the relevant utilisation category, contact endurance and protective measures rather than relying solely on the nominal 12 A rating.
Convenient Plug-In Installation and Maintenance
The Finder 56.34.9.024.0000 is designed for installation using a compatible Finder 96 Series socket. This arrangement allows the relay to be removed and replaced without disconnecting permanent wiring or desoldering components. Depending on the socket selected, the assembly can be installed in a control panel or on a DIN rail.
A lockable test button allows controlled manual operation during suitable commissioning and maintenance procedures, while the mechanical indicator helps technicians identify the relay's contact state. Manual testing can change the condition of connected electrical circuits, so the test facility must only be used when equipment operation is safe and authorised.
Typical Applications
- Industrial automation and machinery control systems.
- 24 V DC electrical control panels.
- Four-circuit auxiliary switching applications.
- Industrial equipment control and electrical interlocking.
- Power management and distribution control assemblies.
- PLC-controlled switching using appropriately rated output interfaces.
- Building automation and facilities management systems.
- Heating, ventilation and air conditioning control equipment.
- Industrial alarm, indication and signalling circuits.
- OEM machinery and electrical equipment manufacturing.
- Serviceable DIN rail relay assemblies using compatible sockets.
- Replacement of compatible Finder 56.34 plug-in relays.