Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Lovato ADXT0506 is an advanced 506 A three-phase soft starter for 380–690 V AC asynchronous motors, featuring a 110–120 V AC or 220–240 V AC auxiliary supply, built-in bypass and support for standard and heavy-duty applications.
£7,544.64
The Lovato ADXT0506 is an advanced three-phase soft starter designed for controlled starting and stopping of large asynchronous motors in standard and heavy-duty industrial applications. As part of the Lovato ADXT soft starter series, it combines three-phase motor control, integrated protection and flexible starting functions to help reduce electrical starting currents and mechanical stress on motors and driven equipment.
The ADXT0506 features a built-in bypass that reduces power losses and heat generation once the motor has completed its starting sequence. It supports both conventional in-line and inside-delta motor connections, providing considerable flexibility when configuring high-power motor-control systems for machinery, process equipment and industrial infrastructure.
With a rated starter current of 506 A and a three-phase 380–690 V AC operational voltage, the ADXT0506 is engineered for high-power industrial motor applications. Its auxiliary supply accepts 110–120 V AC or 220–240 V AC, while the three controlled phases provide smooth acceleration and deceleration for demanding motor-driven equipment.
Soft starters progressively control the electrical power supplied to an AC motor during acceleration and stopping. This helps limit high starting currents and reduces mechanical shock compared with direct-on-line starting, protecting components such as motors, couplings, belts, gearboxes and driven machinery from unnecessary starting stress.
The Lovato ADXT0506 is particularly suited to large motors and demanding loads where controlled acceleration is important. Its three-phase control provides effective management of the starting process, while the built-in bypass improves efficiency after the motor reaches normal operating speed. Support for in-line and inside-delta connections gives system designers additional flexibility when engineering high-power motor-control installations.
Tick the specs you need, then view products that match.
| Motor Protection | Yes | |
|---|---|---|
| Voltage | 400 V, 480 V, 600 V, 690 V | |
| Phase | Three Phase | |
| Coil / Supply Voltage | 110–240 V AC | |
| Current | 506 A | |
| HS Code | 85044090 | |
| Manufacturer | Lovato Electric | |
| Series | ADXT Soft Starters | |
| Model | ADXT0506 | |
| Product type | Advanced three-phase soft starter | |
| Motor type | Asynchronous three-phase | |
| Rated starter current | 506 A | |
| Rated operational voltage | 380–690 V AC | |
| Auxiliary supply voltage | 110–120 V AC / 220–240 V AC | |
| Rated frequency | 50 / 60 Hz | |
| Number of controlled phases | 3 | |
| Built-in bypass | Yes | |
| Connection configurations | In-line / inside delta | |
| Application duty | Standard and heavy duty | |
| In-line current at 3 × Ie for 10 s | 550 A | |
| In-line current at 3.5 × Ie for 15 s | 526 A | |
| In-line current at 4 × Ie for 10 s | 506 A | |
| In-line current at 4 × Ie for 20 s | 427 A | |
| In-line current at 5 × Ie for 5 s | 462 A | |
| Inside-delta current at 3 × Ie for 10 s | 825 A | |
| Inside-delta current at 3.5 × Ie for 15 s | 789 A | |
| Inside-delta current at 4 × Ie for 10 s | 758 A | |
| Inside-delta current at 4 × Ie for 20 s | 640 A | |
| Inside-delta current at 5 × Ie for 5 s | 694 A |
The ADXT0506 provides controlled starting and stopping of large three-phase asynchronous motors in standard and heavy-duty industrial applications, helping reduce starting current and mechanical stress on the motor and driven equipment.
The Lovato ADXT0506 has a rated starter current of 506 A and is designed for high-power industrial motor applications.
The ADXT0506 is designed for three-phase 380–690 V AC motor supplies, making it suitable for a wide range of industrial low-voltage power systems.
Yes. The ADXT0506 incorporates a built-in bypass that reduces power losses and heat generation once the motor has completed its starting sequence.
The ADXT0506 accepts an auxiliary supply of 110–120 V AC or 220–240 V AC, providing flexibility for integration into industrial control systems.
Lovato ADXT soft starters provide industrial engineers, machine builders and panel manufacturers with advanced three-phase motor starting, integrated protection and efficient bypass operation for high-power standard and heavy-duty motor applications.