1SDA100405R1 ABB XT5N 630 Ekip Dip LSIG 630A 4-Pole Fixed MCCB with Front Terminals

1SDA100405R1 ABB XT5N 630 Ekip Dip LSIG 630A 4-Pole Fixed MCCB with Front Terminals

ABB 1SDA100405R1 XT5N 630 Ekip Dip LSIG 630 A four-pole moulded case circuit breaker. Features an electronic LSIG trip unit with long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection. Fixed mounting version with front terminals, 690 V AC rated operational voltage and 36 kA rated service breaking capacity at 415 V AC.

SKU: 1SDA100405R1MPN: 1SDA100405R1
Price
List Price £3,082.34 ex VAT
Your Price (ex VAT)
£3,082.34
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create a trade account to unlock exclusive pricing, special offers and more.

SUBTOTAL (EX VAT) £3,082.34
Trade pricing is personalised to your account

Manufacturer Lead Time

£3,082.34

Why Choose the ABB XT5N 630 Ekip Dip LSIG 630A 4-Pole MCCB?

The ABB XT5N 630 Ekip Dip LSIG, manufacturer order code 1SDA100405R1, is a high-performance 630 A four-pole moulded case circuit breaker (MCCB) designed for reliable circuit protection in low-voltage electrical distribution systems. Part of ABB's SACE Tmax XT5 range, this industrial circuit breaker combines high-current switching capability with an electronic trip unit, fixed mounting and front terminal connections.

Equipped with an Ekip Dip LSIG electronic trip unit, the XT5N 630 provides four essential protection functions: long-time overload protection (L), short-time short-circuit protection (S), instantaneous short-circuit protection (I) and ground-fault protection (G). These functions allow electrical engineers to configure protection settings and coordinate the breaker with other protective devices within a distribution system.

The 630 A rated current makes the ABB 1SDA100405R1 suitable for substantial industrial and commercial power distribution circuits. Its four-pole configuration supports appropriately designed three-phase electrical systems requiring switching of an additional conductor, commonly the neutral.

ABB identifies this exact configuration as XT5N 630 Ekip Dip LSIG In=630 4p F F. The N breaking-capacity version provides a rated service short-circuit breaking capacity of 36 kA at 415 V AC, while the fixed mounting arrangement and front terminals support integration into compatible electrical switchboards and distribution panels.

Key Advantages

  • 630 A rated current for high-capacity low-voltage electrical distribution.
  • Four-pole construction for appropriately designed three-phase systems requiring four-pole switching.
  • Ekip Dip LSIG electronic trip unit provides comprehensive circuit protection.
  • Long-time overload protection (L) helps protect cables and equipment against sustained overcurrent.
  • Short-time short-circuit protection (S) supports protection coordination and selectivity.
  • Instantaneous short-circuit protection (I) provides rapid response to severe faults.
  • Ground-fault protection (G) provides additional protection functionality for suitable electrical systems.
  • 36 kA service breaking capacity at 415 V AC for appropriately rated installations.
  • Adjustable electronic protection settings allow application-specific protection configuration.
  • Fixed circuit breaker design for permanent installation in electrical panels.
  • Front terminal connections support straightforward integration into switchboards.
  • 690 V AC rated operational voltage for a wide range of low-voltage applications.
  • 1000 V rated insulation voltage and 8 kV impulse withstand voltage.
  • ABB SACE Tmax XT5 technology from an established industrial circuit protection range.
  • Electronic protection flexibility compared with basic fixed thermal-magnetic protection.
  • Compact MCCB construction for industrial and commercial distribution systems.

Key Features

  • Manufacturer: ABB.
  • Manufacturer order code: 1SDA100405R1.
  • Product designation: XT5N 630 Ekip Dip LSIG In=630 4p F F.
  • Product family: ABB SACE Tmax XT.
  • Product series: XT5.
  • Product type: Moulded case circuit breaker.
  • Frame size: XT5 630.
  • Rated current (In): 630 A.
  • Number of poles: 4.
  • Breaking-capacity version: N.
  • Trip unit: Ekip Dip LSIG.
  • Long-time protection: L.
  • Short-time protection: S.
  • Instantaneous protection: I.
  • Ground-fault protection: G.
  • Trip technology: Electronic solid-state release.
  • Mounting arrangement: Fixed.
  • Terminal arrangement: Front terminals.
  • Rated operational voltage: 690 V AC.
  • Rated insulation voltage: 1000 V.
  • Rated impulse withstand voltage: 8 kV.
  • Rated service short-circuit breaking capacity at 415 V AC: 36 kA.
  • Rated short-time withstand current: 6 kA.
  • Operating mechanism: Toggle.
  • Degree of protection: IP20 for the breaker itself.
  • Optional motor operation: Available with compatible accessories.
  • EAN: 8056221004824.

Technical Specifications

  • Brand: ABB
  • Manufacturer article number: 1SDA100405R1
  • ABB order code: 1SDA100405R1
  • Manufacturer product description: XT5N 630 Ekip Dip LSIG In=630 4p F F
  • Supplied product group: T-Max XT 250 Range
  • Actual circuit breaker series: ABB SACE Tmax XT5
  • Product category: Moulded case circuit breakers (MCCBs)
  • Product type: Electronic-trip moulded case circuit breaker
  • Frame designation: XT5N 630
  • Frame current: 630 A
  • Rated current (In): 630 A
  • Rated uninterrupted current (Iu): 630 A
  • Number of poles: 4
  • Trip unit model: Ekip Dip LSIG
  • Protection technology: Electronic solid-state release
  • Long-time overload protection (L): Included
  • Short-time short-circuit protection (S): Included
  • Instantaneous short-circuit protection (I): Included
  • Ground-fault protection (G): Included
  • Breaking-capacity classification: N
  • Installation version: Fixed
  • Terminal type: Front terminals
  • Main circuit connection: Bolted connection
  • Operating mechanism: Toggle
  • Rated operational voltage: 690 V AC
  • Rated insulation voltage (Ui): 1000 V
  • Rated impulse withstand voltage (Uimp): 8 kV
  • Rated service short-circuit breaking capacity (Ics) at 220–240 V AC: 70 kA
  • Rated service short-circuit breaking capacity (Ics) at 380–440 V AC: 36 kA
  • Rated service short-circuit breaking capacity (Ics) at 500–525 V AC: 25 kA
  • Rated service short-circuit breaking capacity (Ics) at 690 V AC: 20 kA
  • Rated short-time withstand current (Icw): 6 kA
  • Ultimate short-circuit breaking capacity (Icu): Verify the applicable voltage-dependent ABB rating
  • Degree of protection: IP20
  • Electrical endurance: 5,000 operating cycles
  • Mechanical endurance: 20,000 operating cycles
  • Power loss: 45 W under the manufacturer's stated conditions
  • Integrated motor operator: No
  • Optional motor operator: Compatible accessories available
  • Integrated undervoltage release: No
  • Auxiliary contacts: No auxiliary contacts specified as included
  • Neutral protection configuration: Verify against the Ekip Dip LSIG settings and application requirements
  • Protection adjustment ranges: Refer to the ABB Ekip Dip LSIG technical documentation
  • Product height: 205 mm
  • Product depth: 103.5 mm
  • Product net weight: Approximately 6.4 kg
  • EAN: 8056221004824
  • Relevant product standard: IEC/EN 60947-2
  • Primary application: Low-voltage electrical distribution protection

Advanced 630A Ekip Dip LSIG Electronic Circuit Protection

The ABB XT5N 630 Ekip Dip LSIG is designed to provide dependable protection for high-current low-voltage electrical distribution circuits. Unlike a conventional switch disconnector, this 630 A MCCB automatically interrupts the circuit when its electronic protection system detects fault conditions exceeding the configured thresholds.

The long-time (L) protection function responds to sustained overloads that could otherwise cause excessive conductor heating or equipment damage. Its adjustable settings allow electrical engineers to coordinate the protection characteristic with the design current and current-carrying capacity of the protected circuit.

The short-time (S) protection function provides delayed short-circuit protection, where configured, helping support discrimination between upstream and downstream protective devices. This is particularly valuable in industrial distribution systems where maintaining continuity of supply to unaffected circuits is important. Selectivity must be verified using ABB's published protection curves and the prospective fault-current levels.

The instantaneous (I) protection function responds rapidly to severe short-circuit conditions, while the ground-fault (G) protection function provides an additional protective characteristic for suitable earthing arrangements. The ground-fault function must be configured according to the installation's protection design and should not be confused with a dedicated residual-current device.

The four-pole construction is suitable for appropriately designed three-phase systems where an additional conductor, commonly the neutral, must also be switched. Neutral protection settings and switching requirements depend on the earthing arrangement and applicable electrical regulations.

The fixed mounting arrangement with front terminals is intended for permanent installation in compatible electrical panels and switchboards. The breaker uses a manual toggle operating mechanism and can be equipped with compatible accessories where additional functions are required. The device itself is rated IP20, so suitable panel construction and installation measures must provide the environmental protection required by the installation.

Voltage-Dependent Short-Circuit Breaking Capacity

The ABB XT5N 630 belongs to the N breaking-capacity class within the SACE Tmax XT5 family. Its short-circuit breaking performance depends on the operating voltage, making it essential to verify the electrical characteristics of the installation before selecting the breaker.

For this configuration, published rated service short-circuit breaking capacities (Ics) include 70 kA at 230 V AC, 36 kA at 415 V AC, 25 kA at 500 V AC and 20 kA at 690 V AC. These values must not be applied interchangeably across different voltages.

The rated service breaking capacity (Ics) and ultimate breaking capacity (Icu) are distinct technical characteristics. Electrical designers must confirm that the selected circuit breaker provides suitable short-circuit protection for the prospective fault current at its installation point and coordinate it with upstream and downstream equipment.

With a 1000 V rated insulation voltage, 8 kV rated impulse withstand voltage and 690 V AC rated operational voltage, the XT5N 630 is intended for a broad range of industrial low-voltage distribution applications. Final selection must always account for the installation environment, protection settings, conductor connections and applicable standards.

Typical Applications

  • 630 A low-voltage electrical distribution protection.
  • Three-phase four-pole distribution systems.
  • Industrial main distribution boards.
  • Commercial building electrical switchboards.
  • Manufacturing and production facilities.
  • Industrial machinery supply protection.
  • Electrical control panels and switchgear assemblies.
  • Power distribution circuits requiring adjustable electronic protection.
  • Installations requiring overload, short-circuit and ground-fault protection functions.
  • Industrial plant electrical infrastructure.
  • OEM electrical equipment and switchboard manufacturing.
  • Electrical distribution upgrades requiring a 630 A four-pole electronic-trip MCCB.

Frequently Asked Questions

What is the ABB 1SDA100405R1?

The ABB 1SDA100405R1 is an XT5N 630 four-pole moulded case circuit breaker with a 630 A rated current and an Ekip Dip LSIG electronic trip unit. It is designed for low-voltage electrical distribution protection.

What is the rated current of the ABB XT5N 630 Ekip Dip LSIG?

The breaker has a 630 A rated current (In) and belongs to ABB's XT5N 630 frame range. Its electronic protection settings must be configured to suit the installation.

What does LSIG mean on the ABB Ekip Dip trip unit?

LSIG stands for long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and ground-fault (G) protection.

How many poles does the ABB 1SDA100405R1 have?

The ABB 1SDA100405R1 has four poles. It is suitable for appropriately designed electrical systems requiring four-pole switching and circuit protection.

What does F F mean in the ABB XT5N 630 product description?

The designation F F identifies the fixed circuit breaker version with front terminals, intended for permanent installation in compatible switchboards and electrical panels.

Does the ABB XT5N 630 Ekip Dip LSIG provide ground-fault protection?

Yes. The Ekip Dip LSIG electronic trip unit includes a ground-fault (G) protection function. Its settings and application must be coordinated with the installation's earthing arrangement and protective devices.

What is the short-circuit breaking capacity of the ABB XT5N 630?

The XT5N 630 has a published rated service short-circuit breaking capacity (Ics) of 36 kA at 415 V AC. Other voltage-dependent Ics ratings include 70 kA at 230 V, 25 kA at 500 V and 20 kA at 690 V.

Is the ABB 1SDA100405R1 an MCCB or a switch disconnector?

The ABB 1SDA100405R1 is a moulded case circuit breaker (MCCB). It provides automatic protection against specified overload, short-circuit and ground-fault conditions, as well as manual switching functionality.

Can the ABB XT5N 630 Ekip Dip LSIG be used in an industrial distribution board?

Yes. The breaker is intended for low-voltage electrical distribution applications, including appropriately engineered industrial switchboards and distribution panels. Its breaking capacity, protection settings and installation requirements must be verified.

What should be checked before ordering the ABB 1SDA100405R1?

Confirm the 630 A rated current, four-pole configuration, Ekip Dip LSIG trip unit, fixed front-terminal arrangement, voltage-dependent breaking capacity, neutral protection requirements, connection accessories and installation dimensions against the exact ABB product documentation.

Designed for High-Current Industrial Electrical Distribution

The ABB XT5N 630 Ekip Dip LSIG combines 630 A four-pole circuit protection with adjustable electronic overload, short-circuit and ground-fault functions. Its 36 kA service breaking capacity at 415 V AC, fixed front-terminal configuration and established SACE Tmax XT5 platform make it a practical choice for electrical contractors, switchboard manufacturers, industrial engineers and facilities maintenance professionals.

● Service Agreements

Credit Accounts

Our service agreements are built to support long term procurement relationships. By working closely with engineering teams and procurement departments, we help streamline purchasing processes while ensuring consistent access to critical components and sourcing support when it matters most.

 Priority sourcing and supply support

 Flexible payment terms for qualifying organisations

 Support for engineering, maintenance, and operations

500 +

Stock lines ready to ship

1,000 +

Same day dispatches

3500 +

Customers supported

28 

Trusted Manfacturers

● frequently asked questions

Common questions about our products and support

 

At Led Controls Ltd we help engineers source the right automation and control gear with confidence. below are quick answers to what we are asked most often.

What product ranges do you supply

We supply all leading manfacturers in our industry. we offer next day delivery on most poplour products. 

Can you help specify the correct part?

Your content goes here. Edit or remove this text inline or in the module Content settings. You can also style every aspect of this content in the module Design settings and even apply custom CSS to this text in the module Advanced settings.

Do you have stock for urgent orders?

Your content goes here. Edit or remove this text inline or in the module Content settings. You can also style every aspect of this content in the module Design settings and even apply custom CSS to this text in the module Advanced settings.

What are your delivery times and costs?

Your content goes here. Edit or remove this text inline or in the module Content settings. You can also style every aspect of this content in the module Design settings and even apply custom CSS to this text in the module Advanced settings.

What about warranties, returns and faulty items?

Your content goes here. Edit or remove this text inline or in the module Content settings. You can also style every aspect of this content in the module Design settings and even apply custom CSS to this text in the module Advanced settings.

● latest blog

Discover  our latest insights and
expert advice

From a Simple Idea to Small Business of the Year: The LED Controls Story So Far…

From a Simple Idea to Small Business of the Year: The LED Controls Story So Far…

LED Controls is a specialist distributor of factory automation and industrial controls, supplying OEMs, machine builders, panel builders and end users throughout the UK and worldwide. As a trusted UK distributor for many of the world’s leading automation manufacturers, we provide industrial control products, technical expertise and bespoke automation solutions backed by outstanding customer service.

LED Controls: Danfoss Drives Authorised Partner

LED Controls: Danfoss Drives Authorised Partner

2025 has been a big year for LED Controls, and our blog has expanded accordingly. We've covered a wide range of topics across industrial control and factory automation this year. From core technology explainers and new product releases to panel building best practice...

LED Controls: Your Complete Control Panel Solution

LED Controls: Your Complete Control Panel Solution

2025 has been a big year for LED Controls, and our blog has expanded accordingly. We've covered a wide range of topics across industrial control and factory automation this year. From core technology explainers and new product releases to panel building best practice...