Finder 7P.62.9.009.0485 - 7P Series Surge Protection Devices

Finder 7P.62.9.009.0485 – 7P Series Surge Protection Devices

Finder 7P.62.9.009.0485 is an ultra-slim Type 2+3 RS485 data line surge protection device featuring 8.5 V DC maximum continuous operating voltage, 5 kA nominal discharge current, core-to-core and core-to-earth protection, shield continuity and 7 mm DIN rail construction.

SKU: 7P.62.9.009.0485Alt SKU: 7P6290090485MPN: 7P.62.9.009.0485
Price
List Price £73.67 ex VAT
Your Price (ex VAT)
£73.67
Manufacturer Lead Time Standard Manufacturer Lead Time 6-8 Weeks, Call For Express Delivery Options
Get the best trade prices Trade exclusive

Create a trade account to unlock exclusive pricing, special offers and more.

SUBTOTAL (EX VAT) £73.67
Trade pricing is personalised to your account

Manufacturer Lead Time

£73.67

Why Choose the Finder 7P.62.9.009.0485 Type 2+3 RS485 Data Line Surge Protection Device?

The Finder 7P.62.9.009.0485 is a compact Type 2+3 surge protection device (SPD) specifically designed to protect RS485 communication networks, two-wire data lines and low-voltage signalling interfaces against transient overvoltages. Part of the Finder 7P Series, this specialised surge arrester combines coarse and fine surge suppression to help protect sensitive industrial communication equipment from lightning-induced disturbances and electrical switching transients.

Featuring a 6 V DC nominal voltage, an 8.5 V DC maximum continuous operating voltage (Uc) and a 5 kA nominal discharge current (In), the Finder 7P.62.9.009.0485 provides targeted protection for compatible RS485 data interfaces. Its protection arrangement addresses both longitudinal overvoltages (core-to-earth) and transverse overvoltages (core-to-core), helping reduce the risk of damage to communication transceivers, PLC interfaces, energy meters and industrial monitoring equipment.

With an ultra-slim 7 mm housing width, standard DIN rail mounting and an operating temperature range of −40 to +70 °C, the device is particularly suitable for space-constrained industrial control cabinets. Its serial connection arrangement also supports continuity of the communication cable shield, making it a practical solution for protecting two-wire RS485 networks without unnecessarily complicating the installation.

Key Advantages

  • Dedicated RS485 surge protection: Specifically designed for industrial RS485 communication lines and compatible two-wire data networks.
  • Combined Type 2+3 protection: Integrates coarse and fine surge suppression for sensitive data interfaces.
  • 5 kA nominal discharge current: Provides defined surge-handling performance under the C2 8/20 µs test waveform.
  • 8.5 V DC maximum operating voltage: Suitable for compatible low-voltage data and signalling circuits.
  • Core-to-core protection: Helps limit differential transient voltages between the two signal conductors.
  • Core-to-earth protection: Helps suppress common-mode surges affecting communication conductors relative to protective earth.
  • Fast protection response: Designed to react rapidly to damaging transient overvoltages.
  • Ultra-slim 7 mm construction: Minimises DIN rail space requirements in densely populated control panels.
  • Shield continuity: Supports the connection of shielded two-wire communication cables.
  • Serial installation: Enables protection to be incorporated directly into the communication cable path.
  • PLC and inverter compatibility: Designed for suitable RS485 interfaces used by industrial controllers, inverters and energy meters.
  • Wide temperature range: Suitable for industrial installations operating between −40 and +70 °C.
  • IP20 enclosure protection: Appropriate for installation inside suitably protected electrical cabinets.
  • DIN rail mounting: Simplifies integration into existing automation and electrical control assemblies.
  • Finder engineering: Provides a dedicated surge protection solution from the established Finder 7P product range.

Key Features

  • Finder 7P Series data and signal surge protection device.
  • Product family: 7P.62.
  • Type 2+3 surge protection classification for signal circuits.
  • Designed for RS485 data lines and compatible two-wire telecommunications interfaces.
  • Combination of coarse and fine surge suppression.
  • Nominal operating voltage (Un): 6 V DC.
  • Maximum continuous operating voltage (Uc): 8.5 V DC.
  • Maximum nominal load current (IL): 0.5 A.
  • C2 nominal discharge current (In): 5 kA, 8/20 µs, core-to-core.
  • C2 total discharge current: 10 kA, 8/20 µs, cores-to-earth.
  • Core-to-core voltage protection level: 18 V under C2 testing.
  • Core-to-earth voltage protection level: 30 V under C2 testing.
  • C3 core-to-core voltage protection level: 12 V.
  • C3 core-to-earth voltage protection level: 15 V.
  • Typical response time: 1 ns for core-to-core and core-to-earth protection.
  • Serial resistance per conductor: 1.6 Ω.
  • Specified core-to-core threshold frequency: 1 MHz.
  • Supports shield continuity through the protective device.
  • DIN rail-mounted construction.
  • Compact 7 mm housing width.
  • IP20 ingress protection.
  • Operating temperature range: −40 to +70 °C.
  • Designed in accordance with relevant EN/IEC 61643-21 data-line surge protection requirements.

Technical Specifications

  • Manufacturer: Finder
  • Series: 7P Series
  • Product family: 7P.62
  • Model: 7P.62.9.009.0485
  • Manufacturer part number: 7P.62.9.009.0485
  • Alternative reference: 7P6290090485
  • Product type: Data and signal line surge protection device
  • SPD classification: Type 2+3
  • Protected interface: RS485
  • Number of protected signal conductors: 2
  • Protection modes: Core-to-core and core-to-earth
  • Nominal voltage (Un): 6 V DC
  • Maximum continuous operating voltage (Uc): 8.5 V DC
  • Nominal load current (IL): 0.5 A
  • C2 nominal discharge current (In, 8/20 µs), core-to-core: 5 kA
  • C2 total discharge current (8/20 µs), cores-to-earth: 10 kA
  • C2 voltage protection level (Up), core-to-core: 18 V
  • C2 voltage protection level (Up), core-to-earth: 30 V
  • C3 voltage protection level (Up), core-to-core at 1 kV/µs: 12 V
  • C3 voltage protection level (Up), core-to-earth at 1 kV/µs: 15 V
  • Response time, core-to-core: 1 ns
  • Response time, core-to-earth: 1 ns
  • Serial resistance per core: 1.6 Ω
  • Threshold frequency, core-to-core: 1 MHz
  • Connection arrangement: Serial, with shield continuity
  • Mounting: 35 mm DIN rail
  • Housing width: 7 mm
  • Housing height: 91 mm
  • Housing depth: 58 mm
  • Maximum solid conductor cross-section: 4 mm²
  • Maximum stranded conductor cross-section: 2.5 mm²
  • Ingress protection: IP20
  • Operating temperature: −40 to +70 °C
  • Applicable standard: EN 61643-21 / IEC 61643-21
  • Net weight: Approximately 34.06 g
  • EAN: 8012823413341
  • Country of origin: Czech Republic

Reliable Surge Protection for RS485 Industrial Communication Networks

RS485 communication networks are widely used in industrial automation, energy monitoring, building management and remote control systems. These networks often connect equipment across long cable runs, between separate cabinets or through electrically noisy industrial environments. Lightning-induced disturbances, switching operations and differences in electrical potential can produce transient overvoltages that threaten sensitive communication interfaces.

The Finder 7P.62.9.009.0485 addresses these risks through a combination of coarse and fine surge suppression. Its protection arrangement is designed to limit both differential surges between the two data conductors and common-mode surges between the conductors and protective earth. This dual-mode protection is particularly valuable for RS485 transceivers, where excessive voltage can damage communication circuitry or cause network interruptions.

The device has a 5 kA C2 nominal discharge current for core-to-core protection and a 10 kA total discharge current for the cores-to-earth path. Its specified voltage protection levels of 18 V core-to-core and 30 V core-to-earth under C2 testing help define the residual voltage presented during standardised surge conditions. The additional C3 performance characteristics support fine protection of sensitive communication electronics.

Unlike conventional mains surge protection devices, this model is designed specifically for low-voltage data signals. Its 8.5 V DC maximum continuous operating voltage and 0.5 A nominal load current must be compatible with the connected interface. The specified 1.6 Ω series resistance per conductor and signal frequency characteristics should also be considered when designing communication networks, particularly where long cable runs or higher data rates are involved.

The ultra-slim 7 mm DIN rail housing makes the device suitable for installation in densely populated control cabinets, while the provision for cable shield continuity supports correct treatment of shielded communication wiring. For effective protection, the device should be installed with suitable earthing, appropriate cable routing and connection methods in accordance with Finder's technical documentation and relevant electrical installation standards.

Typical Applications

  • RS485 communication networks: Surge protection for compatible two-wire serial data connections.
  • Industrial PLC systems: Protection of RS485 communication interfaces on programmable logic controllers.
  • Solar inverter communications: Protection of compatible RS485 monitoring and control connections.
  • Energy monitoring systems: Surge protection for electricity meters and data acquisition equipment.
  • Building management systems: Protection of suitable serial communication links between controllers and field devices.
  • SCADA installations: Protection of low-voltage communication interfaces used in supervisory monitoring.
  • Industrial automation cabinets: Compact protection for serial data connections.
  • Remote monitoring equipment: Surge protection for communication circuits serving distributed devices.
  • Lift and elevator controls: Protection of compatible RS485 data connections.
  • Road and tunnel lighting networks: Protection of suitable low-voltage serial communication systems.
  • Industrial process control: Protection of communication links between sensors, controllers and monitoring equipment.
  • Commercial electrical infrastructure: Protection of low-voltage data and signalling circuits.

Frequently Asked Questions

What is the Finder 7P.62.9.009.0485 used for?

The Finder 7P.62.9.009.0485 is a Type 2+3 surge protection device designed to protect RS485 communication networks, two-wire data lines and compatible low-voltage signalling interfaces against transient overvoltages.

Is the Finder 7P.62.9.009.0485 suitable for RS485 networks?

Yes. This model is specifically designed for RS485 data line protection, including compatible interfaces on PLCs, solar inverters, energy meters and industrial monitoring equipment.

What is the maximum continuous operating voltage?

The Finder 7P.62.9.009.0485 has a maximum continuous operating voltage (Uc) of 8.5 V DC and a nominal voltage of 6 V DC.

What is the nominal discharge current rating?

The device has a C2 nominal discharge current of 5 kA for core-to-core protection using the 8/20 µs surge waveform. Its specified total cores-to-earth discharge current is 10 kA.

What does Type 2+3 protection mean for this device?

The Type 2+3 designation describes a combination of coarse and fine surge suppression for data and signal circuits. The device provides protection against transient overvoltages affecting both the signal conductors and their relationship to protective earth.

Does the device protect against both common-mode and differential-mode surges?

Yes. The Finder 7P.62.9.009.0485 provides core-to-core protection against differential-mode surges and core-to-earth protection against common-mode surges.

What are the voltage protection levels?

Under C2 testing, the specified voltage protection levels are 18 V core-to-core and 30 V core-to-earth. Under C3 testing, the corresponding values are 12 V and 15 V.

What is the maximum permitted load current?

The device has a nominal load current of 0.5 A. The connected communication circuit must operate within this limit and the specified voltage characteristics.

Can the Finder 7P.62.9.009.0485 be used on a 230 V AC power circuit?

No. This is a specialised low-voltage data line surge protector with an 8.5 V DC maximum continuous operating voltage. It is not intended to replace an AC mains surge protection device.

How wide is the Finder 7P.62.9.009.0485?

The device has an ultra-slim housing width of approximately 7 mm, making it suitable for compact DIN rail control panel installations.

How is the device installed?

The Finder 7P.62.9.009.0485 mounts on a standard 35 mm DIN rail and is connected in series with the protected two-wire communication line. The installation arrangement supports continuity of the cable shield.

What is the difference between the Finder 7P.62.9.009.0485 and 7P.62.9.036.0005?

The 7P.62.9.009.0485 is intended for compatible RS485 communication circuits with an 8.5 V DC maximum operating voltage, while the 7P.62.9.036.0005 is designed for compatible higher-voltage signalling applications with a 36 V DC maximum operating voltage, including fire detection and telecommunications circuits.

What is the operating temperature range?

The specified operating temperature range is −40 to +70 °C, making the device suitable for a wide range of protected industrial and commercial electrical environments.

Which standards apply to the Finder 7P.62.9.009.0485?

The device is designed in accordance with EN 61643-21 and IEC 61643-21 requirements for surge protection devices connected to telecommunications and signalling networks, including relevant C2 and C3 test classifications.

What should be checked before installing this RS485 surge protector?

Check the communication interface voltage, normal signal levels, nominal load current, operating frequency, cable shield arrangement, protective earthing and the manufacturer's wiring instructions to ensure compatibility with the protected network.

Designed for Professional Industrial Communication Protection

Finder 7P Series data line surge protection devices provide specialised solutions for protecting sensitive industrial communication interfaces against transient overvoltages. Combining Type 2+3 coarse and fine suppression, 5 kA nominal discharge current, low-voltage RS485 compatibility and an ultra-slim 7 mm DIN rail housing, the Finder 7P.62.9.009.0485 supports dependable communication network protection in industrial automation, energy monitoring and building management installations.

● Service Agreements

Credit Accounts

Our service agreements are built to support long term procurement relationships. By working closely with engineering teams and procurement departments, we help streamline purchasing processes while ensuring consistent access to critical components and sourcing support when it matters most.

 Priority sourcing and supply support

 Flexible payment terms for qualifying organisations

 Support for engineering, maintenance, and operations

500 +

Stock lines ready to ship

1,000 +

Same day dispatches

3500 +

Customers supported

28 

Trusted Manfacturers

● frequently asked questions

Common questions about our products and support

 

At Led Controls Ltd we help engineers source the right automation and control gear with confidence. below are quick answers to what we are asked most often.

What product ranges do you supply

We supply all leading manfacturers in our industry. we offer next day delivery on most poplour products. 

Can you help specify the correct part?

Your content goes here. Edit or remove this text inline or in the module Content settings. You can also style every aspect of this content in the module Design settings and even apply custom CSS to this text in the module Advanced settings.

Do you have stock for urgent orders?

Your content goes here. Edit or remove this text inline or in the module Content settings. You can also style every aspect of this content in the module Design settings and even apply custom CSS to this text in the module Advanced settings.

What are your delivery times and costs?

Your content goes here. Edit or remove this text inline or in the module Content settings. You can also style every aspect of this content in the module Design settings and even apply custom CSS to this text in the module Advanced settings.

What about warranties, returns and faulty items?

Your content goes here. Edit or remove this text inline or in the module Content settings. You can also style every aspect of this content in the module Design settings and even apply custom CSS to this text in the module Advanced settings.

● latest blog

Discover  our latest insights and
expert advice

From a Simple Idea to Small Business of the Year: The LED Controls Story So Far…

From a Simple Idea to Small Business of the Year: The LED Controls Story So Far…

LED Controls is a specialist distributor of factory automation and industrial controls, supplying OEMs, machine builders, panel builders and end users throughout the UK and worldwide. As a trusted UK distributor for many of the world’s leading automation manufacturers, we provide industrial control products, technical expertise and bespoke automation solutions backed by outstanding customer service.

LED Controls: Danfoss Drives Authorised Partner

LED Controls: Danfoss Drives Authorised Partner

2025 has been a big year for LED Controls, and our blog has expanded accordingly. We've covered a wide range of topics across industrial control and factory automation this year. From core technology explainers and new product releases to panel building best practice...

LED Controls: Your Complete Control Panel Solution

LED Controls: Your Complete Control Panel Solution

2025 has been a big year for LED Controls, and our blog has expanded accordingly. We've covered a wide range of topics across industrial control and factory automation this year. From core technology explainers and new product releases to panel building best practice...